Features:
Designed to the latest European EN 50171 Specification for Emergency Lighting
True double conversion and PWM technology
Inverter stage output galvanic isolation transformer included
Up to 91% efficiency
Capable of 120% continuous overload to meet European Emergency
Lighting regulations
Parallel mode operation (optional) (hot standby, redundant, symmetric parallel)
Large charger for faster recharge of batteries
Maintenance bypass (for complete isolation of the inverter during maintenance)
Unique Inverter design to suit high inrush lighting loads
Bypass to load (changeover mode) user selection
LCD panel providing accurate detailed information about load, Batteries and
Inverter with advanced diagnostics
RS232 and dry contacts for communication and remote monitoring
PowerPro EL 200 Series
Three Phase Input & Single Phase Output Static Inverter
High Performance Static Inverter
Model EL210 EL215 EL220
Power Rating kVA/kW 10 / 8 15 / 12 20 / 16
Power Factor 0.8
Input
Voltage / Tolerance 230/400 VAC 3phase, 4wires, +ground, +/- 15%
By-pass Voltage 230 VAC single phase
Input Frequency 50Hz +/- 5%
Max RFI EN50091-2 Class A
Output
Voltage 230 VAC single phase
Voltage Stability Static (balanced load) +/-1%, Static (unbalanced load) +/-2%, Dynamic (stop load 0-100%) +/-5%
Voltage Recovery Time After step load 0-100% max. 20ms
Frequency 50Hz
Frequency Tolerance Line synchronised +/- 1% / free running +/- 0.2%
Efficiency at 100% Load >87-91%
Crest Factor 3:1
Short Circuit Protection Electronic short circuit
Overload Capacity 120% continuous, 150% load 10min. 180% 1min, 200% for 1 sec
Total Harmonic Distortion (THD) Linear Load <3% / non linear load (75%NP and CF 3:1) <5%
Batteries
Type Sealed Lead Acid – Maintenance Free
Number of 12V Blocks 30
Float Charging Voltage 405
End of Discharge Voltage 300VDC
Battery Ambient Temperature 25°C
Battery Protection Circuit breaker
Battery Test Automatic battery test once a week
General
Serial Communication Dry contacts plus RS232
Software T-Mon standard / SNMP module optional
Protection Degree IP41
Ambient Operating Temperature / Altitude 0°C to 40°C / <1000m (above sea level)
Standard Emergency Lighting EN 50171
Ventilation Forced air cooling
Relative Humidity 90% max (non-condensing)
Acoustic Noise at 1m distance <56 dbA
Weight (kgs) 200 210 240
Dimensions (mm) w x d x h 520x715x1170