BPC PowerMaster Spécifications Page 15

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 40
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 14
Features:
High input power factor
Low input current THD
High efficiency up to 93%
Cold Start
Static and maintenance bypass
Overload and short circuit protection
Emergency stop utility, built-in
128 recorded event history
Parallel options up to 4 units
Calendar and time indicator
Advanced automatic and manual battery test system
Temperature compensated battery charging
Dial up modem direct connection and AT command set built-in
RS232 and dry contacts for communication and remote monitoring
Input / output customisation optional
SNMP compatible communication
Technical Specification
15
PowerPro CL 300 Range
Three Phase Input & Output Online Transformerless UPS
CleanLine Performance
Model CL310 CL315 CL320 CL330 CL340 CL360 CL380 CL3100 CL3120 CL3160 CL3200 CL3250
Power Rating kVA/kW 10/8 15/12 20/16 30/24 40/32 60/48 80/64 100/80 120/96 160/128 200/160 250/200
Input
Nominal Voltage 230/400 VAC 3 Phase, 4 wire, +/-20%
Bypass Voltage 230/400 VAC 3 Phase, 4 wire, +/-20%
Power Factor >0.98
Input Frequency 50Hz / 60Hz +/- 5%
Input THDi <5%
EMI EN50091-2 Class A
Output
Power Factor 0.8
Voltage 230/400 VAC 3 Phase, 4 Wire, +/-1%
Frequency 50Hz / 60Hz
Frequency Tolerance +/-2% (line synchronised) / +/-0.2% (free running)
Efficiency at 100% Load >91%
Crest Factor 3.1
Overload Protection 100% - 125% load: 10min, 125% - 150% load: 1min, >150% load: bypass
Short Circuit Protection Electronic short circuit protection
Total Harmonic Distortion <3%
Batteries
Type Sealed Lead Acid – Maintenance Free
Number of Batteries 2 x 30 batteries
Float Charging Voltage 2x 405 VDC
End of Discharge Voltage 2x 300 VDC
Battery Cabinet Internal External battery cabinet
Ambient Temperature 25° C
Battery Protection Automatic circuit breaker
Battery Test Standard (every 72 hours)
Options
Transformer Galvanic isolation transformer at the input or output
Parallel Operation 1+3 Systems (N+1 redundant, redundant, symmetric parallel)
General
Software T-mon UPS management software (3 clients standard)
Communication Dry contacts & RS232
Temperature Range 0° C - 40° C
Relative Humidity & Altitude 90% max. (non-condensing) / <1000m above sea level
Protection Degree & Acoustic Noise IP20 / <50dBa (at 1m distance)
Dimensions w x d x h (mm) 375 x 725 x 1030 495 x 835 x 1445 780 x 890 x 1900
Weight (Kgs) 96 105 110 183 196 225 350 350 375 425 435 450
The British Power Conversion Company
Vue de la page 14
1 2 ... 10 11 12 13 14 15 16 17 18 19 20 ... 39 40