19
Model HP305 HP310 HP315 HP320 HP330 HP340 HP360 HP380 HP3100 HP3120 HP3150 HP3200 HP3250 HP3300
Power Rating kVA 5 10 15 20 30 40 60 80 100 120 150 200 250 300
Power Rating kW 4 8 12 16 24 32 48 64 80 96 120 160 200 240
Input
Voltage 230 / 400Vac Three Phase, 4 wires, +ground
Tolerance +/- 15%
By-pass Voltage 230 / 400
Vac Three Phase +/- 10%
Maximum Current absorbed from mains 15.0 19.4 29.1 38.8 58.6 77.9 117.1 156.6 194 233.3 309.8 387.3 486.5 580
Input Frequency / Tolerance 50Hz +/- 5%
EMI
EN50091-2 Class A
Output
Waveform True sine wave / <3% THD
Nominal Voltage 230/400VAC 3 Phase
Voltage Stability (balanced load) +/- 1%
Voltage Stability (unbalanced load) +/- 1%
Voltage Dynamic Step Load (0 to 100% to 0) +/- 5%
Frequency 50
Hz Line synchronised +/- 1% / Free running +/- 0.2%
Frequency Stability Line synchronised +/- 1% Free running +/- 0.2%
On Line Mode Efficiency at full load >90%
Economy Mode Efficiency at full load >98%
Crest Factor 3:1
Over Load Protection 100
% - 125% load for 10min. 125% - 150% load for 1min >150% load by-pass
Total Harmonic Distortion (THD) <3%
Short Circuit Protection
Electronic short circuit protection
Batteries
Type Sealed Lead Acid – Maintenance Free
Number of 12V Blocks 30
Float Charging Voltage 405 Vdc
End of Discharge Voltage 300Vdc
Equalising Boost Charge Voltage 422Vdc
Battery Location External
Battery Test Automatic
General
Protection Degree IP21
Communication Dry contacts plus RS232
Software T-Mon standard, SNMP module optional
Temperature Range 0°C to 40° C
Altitude <1000m (above sea level)
Relative Humidity (non condensed) 90% max
Acoustic Noise at 1m distance <56 dbA <56 dbA <56 dbA <56 dbA <56 dbA <56 dbA <60 dbA <60 dbA <60 dbA <65 dbA <65 dbA <70 dbA <70 dbA <70 dbA
Heat Dissipation at Nominal Load (kW) 0.4 0.8 1.18 1.6 1.8 2.4 3.6 4.8 7.9 9.5 12.7 15.8 19.85 23.7
Dimensions (mm) w x d x h 485x675x1145
570x820x1400 710x800x1400 1100x800x1650 1195x870x1730 1565x925x1880
Weight without Batteries (kgs) 230 235 250 2 66 322 484 562 620 770 810 960 1150 1285 1416
The British Power Conversion Company