PowerPro HP 300 Series
Three Phase Input & Output Online Double Conversion UPS
High Performance Advanced Power Protection
18
BPC UPS in Parallel – One step beyond redundancy
The BPC philosophy is both simple and elegant. UPS outputs are
connected directly to the users distribution system, eliminating
the vulnerable centralised static switch and control circuits.
PowerPro HP can grow with you and give you complete flexibility
whether you are planning to improve system security or increase
your power requirements. Redundant, symmetric and hot
standby modes are all selected from the LCD control panel.
Rectifier Clean Versions
Defining new standards in input power factor correction and reduction
of harmonic currents. Both 12 pulse and 18 pulse clean version
rectifiers are available offering improved power factor correction up
to 0.96 and reducing total harmonic distortion to less then 5%.
Features:
True double conversion technology
Galvanic isolation transformer at the inverter stage
High reliability with low maintenance
Pure sine wave output
High efficiency up to 90%
Intelligent battery monitoring to maximise service life
Automatic static bypass switch providing no-break transfer
Capability for parallel redundant operation if required
LCD panel providing real time operational status
Recorded power history logs
RS232 and dry contacts for communication and remote monitoring
Input / output customisation is available
Model HP305 HP310 HP315 HP320 HP330 HP340 HP360 HP380 HP3100 HP3120 HP3150 HP3200 HP3250 HP3300
Power Rating kVA 5 10 15 20 30 40 60 80 100 120 150 200 250 300
Power Rating kW 4 8 12 16 24 32 48 64 80 96 120 160 200 240
Input
Voltage 230 / 400Vac Three Phase, 4 wires, +ground
Tolerance +/- 15%
By-pass Voltage 230 / 400
Vac Three Phase +/- 10%
Maximum Current absorbed from mains 15.0 19.4 29.1 38.8 58.6 77.9 117.1 156.6 194 233.3 309.8 387.3 486.5 580
Input Frequency / Tolerance 50Hz +/- 5%
EMI
EN50091-2 Class A
Output
Waveform True sine wave / <3% THD
Nominal Voltage 230/400VAC 3 Phase
Voltage Stability (balanced load) +/- 1%
Voltage Stability (unbalanced load) +/- 1%
Voltage Dynamic Step Load (0 to 100% to 0) +/- 5%
Frequency 50
Hz Line synchronised +/- 1% / Free running +/- 0.2%
Frequency Stability Line synchronised +/- 1% Free running +/- 0.2%
On Line Mode Efficiency at full load >90%
Economy Mode Efficiency at full load >98%
Crest Factor 3:1
Over Load Protection 100
% - 125% load for 10min. 125% - 150% load for 1min >150% load by-pass
Total Harmonic Distortion (THD) <3%
Short Circuit Protection
Electronic short circuit protection
Batteries
Type Sealed Lead Acid – Maintenance Free
Number of 12V Blocks 30
Float Charging Voltage 405 Vdc
End of Discharge Voltage 300Vdc
Equalising Boost Charge Voltage 422Vdc
Battery Location External
Battery Test Automatic
General
Protection Degree IP21
Communication Dry contacts plus RS232
Software T-Mon standard, SNMP module optional
Temperature Range 0°C to 40° C
Altitude <1000m (above sea level)
Relative Humidity (non condensed) 90% max
Acoustic Noise at 1m distance <56 dbA <56 dbA <56 dbA <56 dbA <56 dbA <56 dbA <60 dbA <60 dbA <60 dbA <65 dbA <65 dbA <70 dbA <70 dbA <70 dbA
Heat Dissipation at Nominal Load (kW) 0.4 0.8 1.18 1.6 1.8 2.4 3.6 4.8 7.9 9.5 12.7 15.8 19.85 23.7
Dimensions (mm) w x d x h 485x675x1145 570x820x1400 710x800x1400 1100x800x1650 1195x870x1730 1565x925x1880
Weight without Batteries (kgs) 230 235 250 2 66 322 484 562 620 770 810 960 1150 1285 1416